Inverter Compatibility|Joint operation prove-out
We verify DC window, pre-charge, contactor timing, power boundaries, communication, fault response and joint thermal derating between battery and target PCS/inverter.
What must be proven — and who owns each boundary — before claiming joint operation Demo data · COMP-B2.1
| Item | Scope | Owner | Status |
|---|---|---|---|
| Voltage / current / power bounds | Electrical envelope | Battery + PCS | PASS |
| Handshake logic | Start / run / sleep | Battery + PCS | PASS |
| Protection & isolation | Trip → safe state | Battery + PCS + EMS | PASS |
| Comm ICD freeze | CAN / Modbus | All parties | PASS |
| Thermal derate joint | T × SOC × P | Battery + PCS | COND |
| Firmware consistency | Version freeze | All parties | REVIEW |
| Fault recovery path | Latch / clear | Battery + PCS | PASS |
| Evidence pack | Report package | Program | IN PROG |
DC voltage window
Multi-temperature OCV curves vs OVP/UVP and PCS operating window · demo Demo data
OCV–SOC multi-temp overlay (HTML spark · demo)
| Check | Battery | PCS | Result |
|---|---|---|---|
| Max DC | 900 V demo | 900 V | PASS |
| Min DC | 600 V demo | 600 V | PASS |
| OVP margin | ≥ 20 V | Trip 920 V | PASS |
| UVP margin | ≥ 20 V | Trip 580 V | PASS |
| Derate SOC | 5–95% | Matched | COND |
Charge/discharge vs SOC, worst-case table, and DC single-line Demo data
Charge / discharge SOP overlay · HTML spark
| Case | SOC | T | P limit | Note |
|---|---|---|---|---|
| Cold charge | 20% | 0 °C | 0.4C | PCS derate |
| Hot discharge | 80% | 45 °C | 0.8C | Joint thermal |
| Low V edge | 10% | 25 °C | 0.5C | UVP margin |
| High V edge | 95% | 25 °C | 0.3C | OVP margin |
Eleven steps from power-up to soft recovery · with timeout / ACK rules Demo data
Mode boundary logic
Four columns — charge / discharge / standby / derate·fault isolation Demo data
Dynamic response metrics plus fault event → detect → act → recover Demo data
Multi-trace power response (HTML spark)
| Event | Detect | Action | Recover |
|---|---|---|---|
| DC OV | ≤ 20 ms | Trip DC · open | Clear + re-HS |
| OC | ≤ 50 ms | PCS stop | Latch gated |
| Comm loss | 3× HB | Hold → stop | Re-link |
| Thermal | Derate map | Floor P | Cool + clear |
Joint T×SOC power ceiling and A/B/C/N model compatibility Demo data
Temperature × SOC heatmap abstract (HTML cells · demo)
| Model | DC window | Handshake | Fault map | Thermal | Status |
|---|---|---|---|---|---|
| Type A | PASS | PASS | PASS | PASS | PASS |
| Type B | PASS | PASS | COND | PASS | COND |
| Type C | PASS | PLAN | PLAN | PASS | PLAN |
| Type N | REVIEW | PASS | PASS | COND | REVIEW |
From simulation to endurance — target / evidence / result Demo data
Three equal cards — evidence first; optional weak contact link (not a Freeze CTA) Demo data · not a full-width CTA
| Test | Result | Note |
|---|---|---|
| Low-V discharge | PASS | UVP margin |
| High-V charge | PASS | OVP margin |
| Cold start | COND | Pre-charge time |
| Comm drop | PASS | Safe stop |